Skip to product information
1 of 5

800 kW Prime Power Twin Pack Diesel Generator (Scania Engine)

800 kW Prime Power Twin Pack Diesel Generator (Scania Engine)

Request a Quote
Select Phase and Voltage
View full details

Request a Quote

Once you request a quote, we will follow up with current availability, configurations, and delivered pricing.

8 - 16 Week Lead Time
1 Year / 1,000 Hour Warranty - Parts & Service Guidance Included

This 800 kW prime power generator is powered by the Scania DC16 084A 01-01C x2, a 16.4 L turbocharged (vgt) diesel engine configured for dependable continuous-duty and backup power applications. Scania engines are used in demanding commercial and industrial environments where power availability, serviceability, and clear specification review matter.

The alternator package includes Stamford alternator options, with the 480V configuration using the S6L1D-C model where specified. The genset is paired with a Deepsea DSE digital controller for monitoring and fault protection, and is presented in Mulciber's quote-only generator format so voltage, enclosure, delivery, and site requirements can be confirmed before order acceptance.

Prime Power configuration for continuous-duty applications
Deepsea DSE digital controller with monitoring and protection
Stamford alternator options by voltage configuration
Diesel engine package for commercial and industrial power needs
Multiple three-phase voltage configurations
Quote-only review for site-specific requirements
Generator Package Ratings & Configuration
Model
--
Power Node
800 kW
Prime Power Rating
808 kW
Standby Power Rating
--
Rated Voltage
208/240/480/600 V
Frequency/Speed
-- Hz / 1800 rpm
Power Factor
0.8
Phase
3
Available Voltages
208/240/480/600 V 3Ph
Emissions
EPA Tier 4 Final
Scania Engine Technical Specifications
Model
DC16 084A 01-01C x2
Prime Power/Speed
896 kW / 1800 rpm
Standby Power/Speed
-- kW / 1800 rpm
Manufacturer
Scania
Number of Cylinders
8
Cylinder Arrangement
90° V8
Cycle
4-Stroke Diesel
Aspiration
Turbocharged (VGT)
Bore x Stroke (mm x mm)
130 x 154
Displacement
16.4 L
Compression Ratio
16.7:1
Fuel System
XPI Common Rail
Speed Governor
Electronic (EMS)
Cooling System
Liquid (Water-cooled)
Fuel Consumption at 75% Prime Load
161 L/h
Starter Motor
24 V
Stamford Alternator Technical Specifications
Alternator Manufacturer
Stamford
480V Alternator Model
S6L1D-C
208V Alternator Model
S6L1D-D
240V Alternator Model
S6L1D-D
600V Alternator Model
S6L1D-C
480V Prime Amps
1215
208V Prime Amps
2803
240V Prime Amps
2430
600V Prime Amps
972
Exciter Type
PMG (Permanent Magnet Generator)
Power Factor
0.8
Voltage Regulator
MX341
Insulation Grade
H
Protection Grade
IP23
TIF
<50
One-Step Load Acceptance
Full load, one step (per ISO 8528-5)
Deepsea Control Panel Monitoring & Protection DSE Digital Readouts
Deep Sea Electronics - DSE7320 MKII

Monitoring

  • V
  • A
  • Hz
  • kW
  • kVA
  • kVAr
  • PF
  • Engine RPM
  • Oil Pressure
  • Coolant Temp
  • Fuel Level
  • Battery V
  • Run Hours

Communications

  • USB
  • RS232
  • RS485
  • CAN Bus (J1939)
  • Ethernet (via expansion)
  • Modbus RTU
  • DSENet

Protection

  • kW overload protection
  • Reverse power protection
  • Unbalanced load protection
  • Independent Earth Fault trip
  • Charge alternator failure alarm
  • Low fuel alarm
  • Engine over-speed shutdown
  • High coolant temperature shutdown
  • Low oil pressure shutdown

Prime Power Rating

Continuous operation at variable load where supported by the engine rating and site conditions. Final sizing, load profile, emissions suitability, and operating assumptions must be confirmed before order acceptance.

Standby Power Rating

Emergency backup operation at variable load during utility outage. Rated for the duration of the power interruption. No overload permitted unless specifically supported by the confirmed engine rating.

Spec Sheet Download
PDF Datasheet
Options, add-ons, and custom configurations available.
+1 (888) 255-0072
All images are for illustration purposes only. Actual product may vary. Specifications, emissions suitability, options, pricing, and availability must be confirmed by Mulciber before order acceptance.